Show simple item record

dc.creatorGuerrero Sánchez, Anderson E.
dc.creatorCala Amaya, Silvia Liliana
dc.creatorMosquera Montoya, Mauricio
dc.creatorBarrera Hernández, Juan Camilo
dc.creatorPeña Mejía, Cristian Camilo
dc.date2019-05-15
dc.date.accessioned2020-07-25T11:21:43Z
dc.date.available2020-07-25T11:21:43Z
dc.identifierhttps://publicaciones.fedepalma.org/index.php/palmas/article/view/12710
dc.identifier.urihttp://repositorio.fedepalma.org/handle/123456789/140810
dc.descriptionEste artículo presenta los resultados obtenidos en la validación de la metodología de medición del desempeño en el consumo de energía eléctrica en una planta de beneficio de la Zona Norte del país. Para las mediciones se utilizó un analizador de redes Fluke 434 Series II y se registraron parámetros asociados a la energía eléctrica como tensión, intensidad, potencia, factor de potencia, energía activa, energía reactiva, energía aparente y pérdidas asociadas a calidad de la energía eléctrica. Luego de reunir la información, se analizó el desempeño actual del uso de la energía eléctrica desde cuatro puntos de vista: generación o suministro, demanda, consumo y calidad. En el análisis de generación o suministro, se identificó que 62,8 % de la electricidad es proporcionada por sistema de cogeneración, 35,5 % por la red externa y 1,7 % por medio de plantas diésel. A partir de la información histórica de precios, generación o consumos, se estimó un costo ponderado de energía de 218 $/kWh. En el análisis de demanda, se encontró que la planta de beneficio cuenta con 2.357 kW de fuerza motriz instalada, de la cual solo utiliza, en promedio, el 41 %. En cuanto al consumo, se determinaron los valores de kWh con respecto a las toneladas de fruto procesado para cada área que integra la planta de beneficio. El resultado arrojó que el consumo de energía eléctrica para la planta estudiada es de 25,04 kWh/t RFF. El análisis de calidad de la energía determinó que las principales pérdidas son generadas por la energía activa y reactiva. Por último, se concluye que la metodología propuesta es de fácil implementación y permite medir el desempeño del consumo de energía, así como estimar oportunidades de ahorro al mejorar la calidad.es-ES
dc.descriptionThis paper presents the results of a research work aimed at validating a methodology proposed by Cenipalma for measuring the performance of electric power consumption at a palm oil mill (pom). We carried out this research at a pom located in the Colombian Northern Zone, whose  milling capacity is 40 t of fresh fruit bunches per hour. We gathered the data with an energy analyzer (Fluke 434 Series II) at the control room of the mill, where the power system is constantly monitored by staff. We considered parameters associated with electric power, such as voltage, current, power, power factor, active energy, reactive energy, apparent energy, and losses associated to power quality. The data related to the use of electric power was analyzed based on four points of view: source of electric power generation, demand of electric power, consumption of electric power, and quality of electric power. The analysis of the source of power showed that 62.8% of the electric power is provided by the cogeneration system, 35.5% comes from local generation, and 1.7% is supplied through diesel generators. By using the price of electric power according to the type of source, we estimated a weighted cost of 218 COP/kWh. The analysis on the demand of electric power allowed identifying that the palm oil mill under study has 2,357 kW of installed power, although it only uses 41% of this capacity (i.e. 966 kW). The analysis on consumption of electric power yielded an indicator of 25.04 kWh/t FFB. Regarding the power quality analysis, we determined that major losses are due to active energy and reactive energy. Finally, it is concluded that the proposed methodology is quite easy to implement at palm oil mills and that it allows estimating savings opportunities. Our study also provides indication on actions to be taken in order to using electric power more efficiently.en-US
dc.formatapplication/pdf
dc.languagespa
dc.publisherFedepalmaes-ES
dc.relationhttps://publicaciones.fedepalma.org/index.php/palmas/article/view/12710/12614
dc.sourceRevista Palmas; Vol. 39 Núm. 4 (2018); 45-57es-ES
dc.source0121-2923
dc.titleValidación de la metodología de medición del desempeño en el consumo de energía eléctrica en planta de beneficioes-ES
dc.titleAssessment of a Methodology for Measuring the Performance of Electric Power Consumption in Palm Oil Millsen-US
dc.typeinfo:eu-repo/semantics/article